VLF High Voltage Generators

Ultra-Low Frequency Dielectric Loss Tester

Ultra-Low Frequency Dielectric Loss Tester is capable of testing medium-voltage cables in accordance with the relevant standards of the European Committee for Electrotechnical Standardization (CENELEC) harmonization documents HD 620 S1:1996 and HD 621 S1:1996.
A 0.1Hz sine wave voltage of up to 24kV RMS. With this type of cable testing, faults in the insulation, especially water tree damage, can be reliably detected in both polyethylene (PE)/cross-linked polyethylene (XLPE) cables as well as paper-insulated cables, causing flashover. The testing procedure will not damage fault-free insulation. Cables can also be tested for dielectric breakdown strength using both positive and negative DC voltages, as well as trapezoidal AC voltage (rectangular wave voltage). The slew rate of the rectangular wave voltage depends on the cable capacitance and is automatically adjusted. Additional leakage current measurement in DC mode allows for evaluating the relative quality of the cable insulation. The sine wave shape of the system’s test voltage can also be used to directly measure the cable’s dielectric loss factor, thereby determining the degree of deterioration in the cable’s loss factor. For a detailed description of this application, please refer to the relevant manuals.

The Ultra-Low Frequency Dielectric Loss Tester combines the following features and functions:

  • Full AC voltage testing up to 24/31.8 kV RMS (sine wave voltage)
  • Integrated ultra-low-frequency withstand voltage and dielectric loss factor testing
  • Additional output voltage waveforms of DC and rectangular waves
  • Sheath testing and pinpointing up to 10 kV
  • Leakage current measurement
  • Manual and automatic frequency adjustment
  • Voltage breakdown detection with automatic disconnection of the high-voltage connection
  • Logging to internal memory, exportable to a computer via USB stick for generating test reports
  • Firmware updates via USB

Output Voltage 

Model

BVLF-34kV

BVLF-45kV

Output Voltage (Sine Wave)

max.24kVRMS (34kVPEAK)

max.31.8kVRMS (45kVPEAK)

DC Voltage

±1–34kV

±1–45kV

Resolution

0.001kV

0.001kV

Accuracy

1%

1%

 

Output Current

Measurement Range

0–14mA

0–14mA

Resolution

1µA

1µA

Accuracy

1%

1%

Maximum Capacitance Load

0.1Hz@0.5µF/24kVrms/34kVpeak

0.05Hz@1.0µF/24kVrms/34kVpeak

0.01Hz@8.0µF/18kVrms/25kVpeak 

0.1Hz@0.5µF/31.8kVrms/45kVpeak

0.05Hz@1.0µF/31.8kVrms/45kVpeak

0.01Hz@5.0µF/22kVrms/31kVpeak 

Dielectric Loss Factor Measurement (BVLF TD)

VLF-Sine

1-24kV rms

1-31.8kV rms 

Load Range

1nF-8uF

1nF-5uF

Resolution

1×10-5 

1×10 -5 

Accuracy

1×10-4 

1×10-4 

Measurement Range

1×10 -4-9999.9 x10-4 

1×10 -4-9999.9 x10-4 

tan-δ

Measurement Frequency

0.1Hz

0.1Hz

 General Information

Power Consumption

max.300VA

max.400VA

Reverse Voltage Protection

13kV

15kV

Data Interface

USB2.0

Dimensions

(Width x Height xDepth)

Peli Case 1430, 430 mm x 240 mm x 340 mm

Weight

22kg

Ambient

Temperature (Operating)

-10 to +50°C

Storage Temperature

-20 to +60°C

Safety and Electromagnetic Compatibility

(EMC)

Complies with CE standards, Low Voltage Directive (2014/35/EC),

Electromagnetic Compatibility Directive (2014/30/EC), Environmental Impact EN60068-2 and subsequent versions

The user interface

Provides multiple languages

English, Chinese (Simplified), Russian, Spanish, etc.